5.4 Fault Detection Troubleshooting 5 OYMC TOEP C71060622-01-OY V1000 User Manual 185 Cause Possible Solution Control circuit is damaged. Cycle power to the drive. If the problem continues, replace the drive. The power supply was switched off when parameter were written (e.g. using a communications option card). Reinitialize the drive (A1-03). LED Operator Display Fault Name CPF07 Terminal Board Communications Error A communication error occurred at the terminal board. Cause Possible Solution There is a fault connection between the terminal board and control board. Turn the power off and reconnect the control circuit terminals.
LED Operator Display Fault Name CPF08 EEPROM Serial Communication Fault EEPROM communications are not functioning properly. Cause Possible Solution Terminal board or control board is not connected properly. Turn the power off and check the control terminal connections. LED Operator Display Fault Name CPF11 RAM Fault Cause Possible Solution Hardware is damaged. Replace the drive. LED Operator Display Fault Name CPF12 FLASH Memory Fault Problem with the ROM (FLASH memory). Cause Possible Solution Hardware is damaged. Replace the drive. LED Operator Display Fault Name CPF13 Watchdog Circuit Exception Self-diagnostics problem. Cause Possible Solution Hardware is damaged. Replace the drive.