omron — Fault Displays, Causes, and Possible Solutions

5.4 Fault Detection Troubleshooting 5 OYMC TOEP C71060622-01-OY V1000 User Manual 187 Cause Possible Solution Control circuit is damaged. • Cycle power to the drive. Refer to Diagnosing and Resetting Faults on page 222. • If the problem continues, replace the drive. LED Operator Display Fault Name CPF23 PWM Feedback Fault PWM feedback error. Cause Possible Solution Hardware is damaged. Replace the drive. LED Operator Display Fault Name CPF24 Drive Capacity Signal Fault Entered a capacity that does not exist. (Checked when the drive is powered up.) Cause Possible Solution Hardware is damaged. Replace the drive.

LED Operator Display Fault Name dEv Speed Deviation (for Simple V/f with PG) According to the pulse input (RP), the speed deviation is greater than the setting in F1-10 for longer than the time set to F1-11. Cause Possible Solution Load is too heavy. Reduce the load. Acceleration and deceleration times are set too short. Increase the acceleration and deceleration times (C1-01 through C1-08). The load is locked up. Check the machine. Parameters are not set appropriately. Check the settings of parameters F1-10 and F1-11. Motor brake engaged. Ensure the motor brake releases properly.

LED Operator Display Fault Name dWFL FBD’s Fault dWAL FBD’s fault Cause Possible Solution Fault output by a FBD’s program • Correct whatever caused the fault to occur. LED Operator Display Fault Name EF0 Option Card External Fault An external fault condition is present. Cause Possible Solution An external fault was received from the PLC with F6-03 = 3 “alarm only” (the drive continued to run). • Remove the cause of the external fault. • Remove the external fault input from the PLC.