5.4 Fault Detection 188 OYMC TOEP C71060622-01-OY V1000 User Manual Problem with the PLC program. Check the PLC program and correct problems. LED Operator Display Fault Name EF1 External Fault (input terminal S1) External fault at multi-function input terminal S1. EF2 External Fault (input terminal S2) External fault at multi-function input terminal S2. EF3 External Fault (input terminal S3) External fault at multi-function input terminal S3. EF4 External Fault (input terminal S4) External fault at multi-function input terminal S4. EF5 External Fault (input terminal S5) External fault at multi-function input terminal S5.
EF6 External Fault (input terminal S6) External fault at multi-function input terminal S6. Cause Possible Solution An external device has tripped an alarm function. Remove the cause of the external fault and reset the fault. Wiring is incorrect. • Ensure the signal lines have been connected properly to the terminals assigned for external fault detection (H1- = 20 to 2F). • Reconnect the signal line. Incorrect setting of multi-function contact inputs. • Check if the unused terminals set for H1- = 20 to 2F (External Fault). • Change the terminal settings. LED Operator Display Fault Name Err EEPROM Write Error Data does not match the EEPROM being written to.
Cause Possible Solution - • Press the button. • Correct the parameter settings. • Cycle power to the drive. Refer to Diagnosing and Resetting Faults on page 222. LED Operator Display Fault Name FbH Excessive PID Feedback PID feedback input is greater than the level set b5-36 for longer than the time set to b5-37. To enable fault detection, set b5-12 = “2” or “5”. Cause Possible Solution Parameters are not set appropriately. Check the settings of parameters b5-36 and b5-37. Wiring for PID feedback is incorrect. Correct the wiring.