omron — Fault Displays, Causes, and Possible Solutions

5.4 Fault Detection OYMC TOEP C71060622-01-OY V1000 User Manual 189 There is a problem with the feedback sensor. • Check the sensor on the control side. • Replace the sensor if damaged. LED Operator Display Fault Name FbL PID Feedback Loss This fault occurs when PID Feedback Loss Detection is programmed to fault (b5-12 = 2) and the PID Feedback Cause Possible Solution Parameters are not set appropriately. Check the settings of parameters b5-13 and b5-14. Wiring for PID feedback is incorrect. Correct the wiring. There is a problem with the feedback sensor. Check the sensor on the controller side. If damaged, replace the sensor.

LED Operator Display Fault Name GF Ground Fault • Current shorted to ground exceeded 50% of rated current on output side of the drive. • Setting L8-09 to 1 enables ground fault detection in models 5.5 kW or larger. Cause Possible Solution Motor insulation is damaged. • Check the insulation resistance of the motor. • Replace the motor. 5 A damaged motor cable is creating a short circuit. • Check the motor cable. • Remove the short circuit and turn the power back on. • Check the resistance between the cable and the ground terminal . • Replace the cable. The leakage current at the drive output is too high. • Reduce the carrier frequency. • Reduce the amount of stray capacitance.

The drive started to run during Current Offset Fault or while coasting to a stop. • The value set exceeds the allowable setting range while the drive automatically adjusts the current offset (this happens only attempting to restart a PM motor that is coasting to stop). • Enable Speed Search at start (b3-01 = 1). • Perform Speed Search 1 or 2 (H1-xx = 61 or 62) via one of the external terminals. Note: Speed Search 1 and 2 are the same when using PM OLV. Hardware problem. • Replace the drive. LED Operator Display Fault Name LF Output Phase Loss • Phase loss on the output side of the drive. • Phase Loss Detection is enabled when L8-07 is set to “1” or “2”.

Cause Possible Solution The output cable is disconnected. • Check for wiring errors and ensure the output cable is connected properly. • Correct the wiring.