omron — Auto-Tuning Codes, Causes, and Possible Solutions

5.7 Auto-Tuning Fault Detection 5.7 Auto-Tuning Fault Detection Auto-Tuning faults are shown below. When the following faults are detected, the fault is displayed on the Digital Operator and the motor coasts to a stop. No fault or alarm outputs will occur ◆ Auto-Tuning Codes, Causes, and Possible Solutions Table 5.11 Auto-Tuning Codes, Causes, and Possible Solutions 218 OYMC TOEP C71060622-01-OY V1000 User Manual LED Operator Display Error Name Er-01 Motor Data Error Cause Possible Solutions Motor data or data entered during Auto-Tuning incorrect. • Check that the motor data entered to the T1 parameters match the information written on the motor nameplate input before Auto-Tuning.

• Start Auto-Tuning over again and enter the correct information. Motor output and motor-rated current settings (T1-02 and T1-04) do not match. • Check the drive and motor capacities. • Correct the settings of parameters T1-02 and T1-04. Motor output and no-load current settings (T1-04 and E2-03) do not match. This data is required only when Auto-Tuning for Open Loop Vector Control or when performing Stationary Auto-Tuning. • Check the motor-rated current and no-load current. • Correct the settings of parameters T1-04 and E2-03. Base frequency and base motor rotations (T1-05 and T1-07) do not match. Set T1-05 and T1-07 to the correct value.

LED Operator Display Error Name Er-02 Minor Fault Cause Possible Solutions Motor data entered during Auto-Tuning was incorrect. • Motor data entered to the T1 parameters does not match the information written on the motor nameplate. Enter the correct data. • Start Auto-Tuning over again and enter the correct information. The wiring is faulty. • Check the wiring and correct defective connections. • Check around the machine. • Check the load. • Use the information on page 237 to find out what caused the problem. Load is too heavy. LED Operator Display Error Name Er-03 STOP Button Input