omron — oPE Codes, Causes, and Possible Solutions

5.6 Operator Programming Errors Troubleshooting 5 OYMC TOEP C71060622-01-OY V1000 User Manual 217 Cause Possible Solutions The following simultaneous contradictory settings: C6-05 is greater than 6 and C6-04 is greater than C6-03 (carrier frequency lower limit is greater than the upper limit). If C6-05 is less than or equal to 6, the drive operates at C6-03. Correct the parameter settings. Upper and lower limits between C6-02 and C6-05 contradict each other. LED Operator Display Error Name oPE13 Pulse Monitor Selection Error Incorrect setting of monitor selection for Pulse Train (H6-06).

Cause Possible Solutions Scaling for the Pulse Train monitor is set to 0 (H6-07 = 0) while H6-06 is not set to 101, 102, 105, or 116. Change scaling for the Pulse Train monitor or set H6-06 to 101, 102, 105, or 116. LED Operator Display Error Name oPE14 Application setting error Incorrect setting in combination with simple positioning stop or Bi-directional output conversion.

Cause Possible Solutions Parameter b1-03 = 9 (simple positioning stop) and • Drive is not initialized to European settings (o2-09 is not 2) • Dwell function is activated (b6-03 or b6-04 are not 0) • the KEB function is activated (H1-†† = 65/66/7A/7B) • Stall prevention during deceleration is enabled (L3-04 is not 0) • Over voltage suppression is enabled (L3-11 = 1) • High slip braking is enabled (H1-†† = 68) • An S-curve is applied to the deceleration ramp (C2-03 and C2-04 are not 0) PID output or frequency reference to bi-directional output frequency reference is enabled (d4-11 = 1) and the drive is not initialized to European settings. Check the initialization mode in parameter o2-09.

Correct the parameter settings.