5.6 Operator Programming Errors 216 OYMC TOEP C71060622-01-OY V1000 User Manual Cause Possible Solutions Attempted to use a function in the V/f motor control method that is only possible in Open Loop Vector Control. Check the motor control method and the functions available. Simple V/f with PG was enabled while not in V/f Control (H6-01 = 3). To use Simple V/f with PG, ensure the motor control method has been set to V/f Control (A1-02 = “0”). In Open Loop Vector Control, n2-02 is greater than n2-03 Correct parameter settings so that n2-02 is less than n2-03. In Open Loop Vector Control, C4-02 is greater than C4-06 Correct parameter settings so that C4-02 is less than C4-06.
In PM Open Loop Vector Control, parameters E5-02 to E5-07 are set to 0. • Set the correct motor code in accordance with the motor being used (E5-01). • When using a special-purpose motor, set E5- in accordance with the Test Report provided. The following conditions are true in PM Open Loop Vector Control: E5-03 does not equal 0 E5-09 and E5-24 are both equal to 0, or neither equals 0 Set E5-09 or E5-24 to the correct value, and set the other to “0”. Set the motor-rated current for PM to “0” (E5-03). Note: Use U1-18 to find which parameters are set outside the specified setting range. Other errors are given precedence over OPE08 when multiple errors occur at the same time.
LED Operator Display Error Name oPE09 PID Control Selection Fault PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1 to 4). Cause Possible Solutions The following simultaneous contradictory settings: b5-15 not 0.0 (PID Sleep Function Operation Level) The stopping method is set to either DC injection braking or coast to stop with a timer (b1-03 = 2 or 3). • Set b5-15 to another value besides 0. • Set the stopping method to coast to stop or ramp to stop (b1-03 = “0” or “1”). LED Operator Display Error Name oPE10 V/f Data Setting Error The following setting errors have occurred where:
E1-04 is greater than or equal to E1-06 is greater than or equal to E1-07 is greater than or equal to E1-09. Or the following setting errors have occurred: E3-04 is greater than or equal to E3-06 is greater than or equal to E3-07 is greater than or equal to E3-09. Cause Possible Solutions — Correct the settings for E1-04, -06, -07 and -09 (or E-04, -06, -07, -09 for motor 2). LED Operator Display Error Name oPE11 Carrier Frequency Setting Error Correct the setting for the carrier frequency.