5.6 Operator Programming Errors Troubleshooting 5 OYMC TOEP C71060622-01-OY V1000 User Manual 215 Cause Possible Solutions The drive, control board, or terminal board has been replaced and the parameter settings between the control board and the terminal board no longer match. To load the parameter settings to the drive that are stored in the terminal board, set A1-03 to 5550. Initialize parameters after drive replacement by setting A1-03 to 1110 or 2220. LED Operator Display Error Name oPE05 Run Command Selection Error The Run command selection parameter b1-02 is set to 3 but no option board is installed.
Cause Possible Solutions Frequency reference is assigned to an option card (b1-01 = 3) that is not connected to the drive. Reconnect the option card to the drive. The Run command is assigned to an option card (b1-02 = 3) that is not connected to the drive. Frequency reference is assigned to the pulse train input (b1-01 = 4), but terminal RP is not set for pulse train input (H6-01 is greater than 0). Set H6-01 to “0”. LED Operator Display Error Name oPE07 Multi-Function Analog Input Selection Error A contradictory setting is assigned to multi-function analog inputs H3-02 through to H3-10 and PID functions conflict. Cause Possible Solutions H3-02 and H3-10 are set to the same value.
Change the settings to H3-02 and H3-10 so that functions no longer conflict. Note: Both 0 (primary analog frequency reference) and F (Not Used) can be set to H3-02 and H3-10 at the same time. The following simultaneous contradictory settings: H3-02 or H3-10 = B (PID Feedback) and H6-01 (Pulse Train Input) = 1 (PID Feedback) Disable one of the PID selections. The following simultaneous contradictory settings: H3-02 or H3-10 = C (PID Target Value) and H6-01 = 2 (pulse train input sets the PID target value) The following simultaneous contradictory settings:
H3-02 or H3-10 = C (PID Target Value) and b5-18 = 1 (enables b5-19 as the target PID value) The following simultaneous contradictory settings: H6-01 or H3-10 = C (PID Target Value) and b5-18 = 1 (enables b5-19 as the target PID value) LED Operator Display Error Name oPE08 Parameter Selection Error A function has been set that cannot be used in the motor control method selected.