omron — oPE Codes, Causes, and Possible Solutions

5.6 Operator Programming Errors 214 OYMC TOEP C71060622-01-OY V1000 User Manual • Run /Stop command for 2-wire sequence 2 was set (H1-†† = 42), but forward/reverse command (H1-†† = 43) was not. • “Drive Enable” is set to multi-function input S1 or S2 (H1-01 = 6A or H1-02 = 6A). Correctly set functions that need to be enabled in combination with other functions. • Two of the following functions are set at the same time: • Up / Down Command (10 vs. 11) • Up 2 / Down 2 Command (75 vs.

76) • Hold Accel/Decel Stop (A) • Analog Frequency Reference Sample / Hold (1E) • Offset Frequency 1, 2, 3 Calculations (44, 45, 46) • Check if contradictory settings have been assigned to the multi-function input terminals at the same time. • Correct setting errors. The Up/Down command (10, 11) is enabled at the same time as PID control (b5-01). Disable control PID (b5-01 = “0”) or disable the Up/ Down command. • One of the following settings at the multi-function input terminals: • External Search Command 1 and External Search Command 2 (61 vs. 62) • Fast-Stop N.O. and Fast-Stop N.C. (15 vs. 17) • KEB for Momentary Power Loss and High Slip Braking (65, 66, 7A, 7B vs.

68) • Motor Switch Command and Accel/Decel Time 2 (16 vs. 1A) • KEB Command 1 and KEB Command 2 (65, 66 vs. 7A, 7B) • FWD Run Command (or REV) and FWD/REV Run Command (2-wire) (40, 41 vs. 42, 43) • External DB Command and Drive Enable (60 vs. 6A)) • Motor Switch Command and UP2/DOWN2 Command (16 vs. 75, 76) Check for contradictory settings assigned to the multi-function input terminals at the same time. Correct setting errors. • One of the following settings was entered while H1-†† = 2 (External Reference 1/2):

• b1-15 = 4 (Pulse Train Input) and H6-01 (Pulse Train Input Function Selection) not = 0 (Frequency Reference) • b1-15 or b1-16 set to 3 but no option card connected • Although b1-15 = 1 (Analog Input) and H3-02 or H3-10 are set to 0 (Frequency Bias). Correct the settings for the multi-function input terminal parameters. H2-†† = 38 (Drive Enabled) but H1-†† is not set to 6A (Drive Enable). H1-†† = 7E (Direction Detection) although H6-01 is not set to 3 (Simple V/f with PG). LED Operator Display Error Name oPE04 Initialization required.