omron — oPE Codes, Causes, and Possible Solutions

5.6 Operator Programming Errors 5.6 Operator Programming Errors An Operator Programming Error (oPE) occurs when an inappropriate parameter is set or an individual parameter setting is inappropriate. The drive will not operate until the parameter is set correctly; however, no alarm or fault outputs will occur. If an oPE occurs, investigate the cause and refer to Table 5.10 for the appropriate action. When oPE error is displayed, press the ENTER button to display U1-34 (oPE fault constant). This monitor displays the parameter causing the oPE error.

◆ oPE Codes, Causes, and Possible Solutions Table 5.10 oPE Codes, Causes, and Possible Solutions Troubleshooting 5 OYMC TOEP C71060622-01-OY V1000 User Manual 213 LED Operator Display Error Name oPE01 Drive Capacity Setting Fault Drive capacity and then value set to o2-04 do not match. Cause Possible Solutions The drive capacity setting (o2-04) and the actual capacity of the drive are not the same. Correct the value set to o2-04. LED Operator Display Error Name oPE02 Parameter Range Setting Error Use U1-18 to find which parameters were set outside the setting range. Cause Possible Solutions Parameters were set outside the possible setting range. Set parameters to the proper values. Note:

Other errors are given precedence over oPE02 when multiple errors occur at the same time. LED Operator Display Error Name oPE03 Multi-Function Input Selection Error A contradictory setting is assigned to multi-function contact inputs H1-01 through to H1-06. Cause Possible Solutions • The same function is assigned to two multi-function inputs. • Excludes “Not used” and “External Fault.” • Ensure all multi-function inputs are assigned to different functions. • Re-enter the multi-function settings to ensure this does not occur. The Up command was set but the Down command was not, or vice versa (settings 10 vs. 11).

Correctly set functions that need to be enabled in combination with other functions. The Up 2 command was set but the Down 2 command was not, or vice versa (settings 75 vs. 76).