omron — Alarm Codes, Causes, and Possible Solutions

5.5 Alarm Detection 212 OYMC TOEP C71060622-01-OY V1000 User Manual LED Operator Display Minor Fault Name Uv Undervoltage • One of the following conditions was true when the drive was stopped and a run command was entered: • DC bus voltage dropped below the level specified in L2-05. • Contactor to suppress inrush current in the drive was open. • Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus voltage is under L2-05. Cause Possible Solutions Minor Fault (H2- †† = 10) Phase loss in the drive input power. Check for wiring errors in the main circuit drive input power. Correct the wiring. YES Loose wiring in the drive input power terminals.

• Ensure the terminals have been properly tightened. • Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Gauges and Tightening Torque on page 59 YES There is a problem with the drive input power voltage. • Check the voltage. • Lower the voltage of the drive input power so that it is within the limits listed in the specifications. YES Drive internal circuitry is worn. • Check the maintenance time for the capacitors (U4-05). • Replace the drive if U4-05 exceeds 90%. YES The drive input power transformer is not large enough and voltage drops when the power is switched on.

• Check for a tripped alarm when the magnetic contactor, line breaker and leakage breaker are turned on. • Check the capacity of the drive input power transformer. YES Air inside the drive is too hot. • Check the temperature inside the drive. YES The CHARGE indicator light is broken or disconnected. • Replace the drive. YES