5.5 Alarm Detection Troubleshooting 5 OYMC TOEP C71060622-01-OY V1000 User Manual 211 LED Operator Display Minor Fault Name PGo PG Disconnect (for Simple V/f with PG) Detected when no PG pulses received for a time longer than setting in F1-14. Cause Possible Solutions Minor Fault Output (H2- = 10) Pulse input (RP) is disconnected. Reconnect the pulse input (RP). YES Pulse input (RP) wiring is wrong. Correct the wiring. YES Motor brake is engaged. Ensure the brake releases properly YES LED Operator Display Minor Fault Name rUn Motor Switch during Run A command to switch motors was entered during run.
Cause Possible Solutions Minor Fault Output (H2- = 10) A motor switch command was entered during run. Change the operation pattern so that the motor switch command is entered while the drive is stopped. YES LED Operator Display Minor Fault Name UL3 Undertorque Detection 1 Drive output current (or torque in OLV) less than L6-02 for longer than L6-03 time. Cause Possible Solutions Minor Fault (H2- = 10) Inappropriate parameter settings. Check parameters L6-02 and L6-03. YES Load has dropped or decreased significantly. • Check for broken parts in the transmission system.
YES LED Operator Display Minor Fault Name UL4 Undertorque Detection 2 Drive output current (or torque in OLV) less than L6-05 for longer than L6-06 time. Cause Possible Solutions Minor Fault (H2- = 10) Inappropriate parameter settings. Check parameters L6-05 and L6-06. YES The load has dropped or decreased significantly. • Check for broken parts in the transmission system. YES