5.5 Alarm Detection 210 OYMC TOEP C71060622-01-OY V1000 User Manual Cause Possible Solutions Minor Fault Output (H2- = 10) Overshoot or undershoot is occurring. • Adjust the gain by using the pulse train input parameters (H6- 02 through H6-05). Adjust the speed feedback accuracy. • Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control Integral Time 1). YES PG pulse settings are incorrect. Set the H6-02 (Pulse Train Input Scaling) = 100%, the number of pulses during maximum motor revolutions. YES Parameter settings are inappropriate. Check the setting for the overspeed detection level and the overspeed detection time (F1-08 and F1-09).
YES LED Operator Display Minor Fault Name ov DC Bus Overvoltage The DC bus voltage exceeded the trip point. For 200 V class: approximately 410 V For 400 V class: approximately 820 V (740 V when E1-01 Cause Possible Solutions Minor Fault (H2- = 10) Surge voltage present in the drive input power. • Install a DC reactor or an AC reactor. • Voltage surge can result from a thyristor convertor and a phase advancing capacitor operating on the same drive input power system. YES • The motor has short- circuited. • Ground current has over-charged the main circuit capacitors via the drive input power. • Check the motor power cable, relay terminals and motor terminal box for short circuits.
• Correct grounding shorts and turn the power back on. YES Noise interference causes the drive to operate incorrectly. • Review possible solutions for handling noise interference. • Review section on handling noise interference and check control circuit lines, main circuit lines and ground wiring. • If the magnetic contactor is identified as a source of noise, install a surge protector to the MC coil. YES Set number of fault restarts (L5-01) to a value other than 0. YES LED Operator Display Minor Fault Name PASS MEMOBUS/Modbus Comm. Test Mode Complete Cause Possible Solutions Minor Fault Output (H2- = 10) MEMOBUS/Modbus test has finished normally.
This verifies that the test was successful. No output