5.9 Troubleshooting without Fault Display ■ Motor Operates at a Higher Speed than the Speed Command ■ Poor Speed Control Accuracy Above Base Speed in Open-Loop Vector Motor Control Method Troubleshooting 5 ■ Peripheral Devices Affected by Drive Operation ■ Ground Fault Interrupter Activates When Drive is Running OYMC TOEP C71060622-01-OY V1000 User Manual 237 Cause Possible Solution PID is enabled. If the PID mode is enabled (b5-01 = 1 to 4), the drive output frequency will change to regulate the process variable to the target setpoint. The PID can command a speed up to maximum output frequency (E1-04). If PID operation is not target, disable PID by setting b5-01 = “0”.
Cause Possible Solution The maximum output voltage of the drive is determined by its input voltage. Vector control uses voltage to control the currents within the motor. If the vector control voltage reference value exceeds the drive output voltage capability, the speed control accuracy will decrease because the motor currents cannot be properly controlled. Use a motor with a lower rated voltage compared to the input voltage. Cause Possible Solutions Radio frequency interference may be generated by drive output PWM waveform. • Change the Carrier Frequency Selection (C6-02) to lower the carrier frequency. This will help to reduce the amount of transistor switching noise.
• Install an Input Noise Filter at the input power terminals. • Install an Output Noise Filter at the motor terminals. • Use conduit. Metal can shield electrical noise. • Ground the drive and motor. • Separate main circuit wiring from control wiring. Cause Possible Solutions The output of the drive is a series of high frequency pulses (PWM), so there is a certain amount of leakage current. This may cause the ground fault interrupter to operate and cut off the drive input power.
• Change to a ground fault interrupter with a higher leakage current detection level (such as, a sensitivity current of 200 mA or greater per Unit, with an operating time of 0.1 s or more), or one that incorporates high-frequency countermeasures. • Change the Carrier Frequency Selection (C6-02) to lower the carrier frequency. Note: Leakage current increases in proportion to cable length.