5.9 Troubleshooting without Fault Display Pressed ■ Motor Does Not Operate When an External Run Command is Input ■ Motor Stops During Acceleration or When a Load is Connected ■ Motor Rotates in One Direction Only 236 OYMC TOEP C71060622-01-OY V1000 User Manual Cause Possible Solutions The LOCAL/REMOTE mode is not selected properly. Press the LOCAL/REMOTE button to switch. The LO/RE LED should be on for LOCAL mode. The drive is not in drive mode. A run command will not be issued. Exit to the drive mode and cycle the run command. The frequency reference is too low. • If the frequency reference is set below the frequency set in E1-09 (Minimum Output Frequency), the drive will not operate.
• Raise the frequency reference to at least the minimum output frequency. Cause Possible Solutions The LOCAL/REMOTE mode is not selected properly. Press the LOCAL/REMOTE button to switch. The LO/RE LED should be off for REMOTE mode. The drive is not in Drive Mode. A run command will not be issued. Exit to the Drive mode and cycle the run command. The frequency reference is too low. • If the frequency reference is set below the frequency set in E1-09 (Minimum Output Frequency), the drive will not operate. • Raise the frequency reference to at least the minimum output frequency. Cause Possible Solution • The load is too heavy.
• The limit of motor response may be reached during rapid acceleration. This may be a result of improper stall prevention or automatic torque boost function adjustment. (L3-01 = 2) Increase the acceleration time (C1-01) or reduce the motor load. Also, consider increasing the motor size and/or drive size. Cause Possible Solution "Reverse run prohibited" is selected. If b1-04 (Reverse Prohibit Operation) is set to 1 (reverse run prohibited), the drive will not accept a reverse run command. Set b1-04 = “0” to allow reverse run operation.