5.9 Troubleshooting without Fault Display ■ Output Frequency is not as High as Frequency Reference ■ Buzzing Sound from Motor at 2 kHz Troubleshooting 5 ■ Unstable Motor Speed when Using PM or IPM ■ Motor Does Not Operate When the RUN Button on the Digital Operator is OYMC TOEP C71060622-01-OY V1000 User Manual 235 Cause Possible Solutions Frequency reference is set within the range of the Jump Frequency. • Adjust the parameters used for the Jump Frequency function (d3-01 through d3-03). • Enabling the Jump Frequency prevents the drive from outputting the frequencies specified in the Jump Frequency range. Upper limit for the frequency reference has been exceeded.
• Set the maximum output frequency and the upper limit for the frequency reference to more appropriate values (E1-04, d2-01). • The following calculation yields the upper value for the output frequency = E1-04 × d2-01 / 100 Large load triggered Stall Prevention function during acceleration. • Reduce the load. • Adjust the Stall Prevention level during acceleration (L3-02). Cause Possible Solutions Exceeded 110% of the rated output current of the drive while operating at low speeds. • If the output current rises too high at low speeds, the carrier frequency automatically reduces and causes a whining or buzzing sound.
• If the sound is coming from the motor, disable carrier frequency derating (L8-38 = “0”). • Disabling the automatic carrier frequency derating increases the chances of an overload fault (oL2). Switch to a larger capacity motor if oL2 faults occur too frequently. Cause Possible Solutions The motor code for PM (E5-01) is set incorrectly. (Yaskawa motors only) Set parameter E5-01 in accordance with the motor being used. The drive is operating at less than 10% of the speed reference. Consult with OYMC about using a different type of motor when attempting to operate at 10% of the speed reference. Motor hunting occurs. Set and carefully adjust the following parameters in the order listed:
n8-45 (Speed Feedback Detection Suppression Gain) n8-55 (Load Inertia for PM Motors) C4-02 (Torque Compensation Primary Delay Time) Hunting occurs at start. Increase the S-curve time at the start of acceleration (C2-01). Too much current is flowing through the drive. If using a PM motor, set the correct motor code to E5-01. If using a specialized motor, set parameter E5-xx to the correct value according to the Motor Test Report.