omron — Recommended Daily Inspection

6.2 Inspection ◆ Recommended Daily Inspection Table 6.1 outlines the recommended daily inspection for OYMC drives. Check the following items on a daily basis to avoid premature deterioration in performance or product failure. Copy this checklist and mark the “Checked” column after each inspection. WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc.

To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level. Table 6.1 General Recommended Daily Inspection Checklist 244 OYMC TOEP C71060622-01-OY V1000 User Manual Inspection Category Inspection Points Corrective Action Checked Motor • Inspect for abnormal oscillation or noise coming from the motor. • Check the load coupling • Measure motor vibration • Tighten all loose components Cooling • Inspect for abnormal heat generated from the drive or motor and visible discoloration.

• Check for excessive load • Loose connections • Check for dirty heatsink or motor • Ambient temperature Cooling • Inspect drive cooling fan operation. • Check for clogged or dirty fan. • Check fan operation drive parameter. Environment • Verify the drive environment complies with the specifications listed in the Installation section of this manual. • Eliminate the source of contaminants or correct poor environment. Load • The drive output current should not be higher than the motor or drive rating for an extended period of time. • Check for excessive load. • Check the motor parameter settings of the drive. Power Supply Voltage • Check main power supply and control voltages.

• Correct the voltage or power supply to within nameplate specifications. • Verify all main circuit phases.