omron — Recommended Periodic Inspection

6.2 Inspection ◆ Recommended Periodic Inspection Table 6.2 outlines the recommended periodic inspections for OYMC drive installations. Periodic inspections should generally be checked every 3-6 months; however, the drive may require more frequent inspection due to poor environments or rigorous use. Operating and environmental conditions, along with experience in each application, will determine the actual inspection frequency for each installation. Periodic inspection will help to avoid premature deterioration in performance or product failure. Copy this checklist and mark the “Checked” column after each inspection. WARNING! Electrical Shock Hazard.

Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.

■ Periodic Inspection Table 6.2 Periodic Inspection Checklist Periodic Inspection & Maintenance 6 OYMC TOEP C71060622-01-OY V1000 User Manual 245 Inspection Area Inspection Points Corrective Action Checked Main Circuit Periodic Inspection General • Overall check of the main power circuit and ground terminals Take appropriate actions (e.g., tightening loose connections). • Inspect equipment for discoloration from overheating or deterioration. • Inspect for damaged or deformed parts. • Replace damaged components as required. • The drive has few serviceable parts and may require complete drive replacement. • Inspect for dirt, foreign particles, or dust collection on components.

• Inspect enclosure door seal if present. Replace components if cleaning is not possible. • Use dry air to clear away foreign matter. Use a pressure of 39.2 x 104 to 58.8 x 104 Pa (4 - 6 kg •cm2). Conductors and Wiring • Inspect wiring and connections for discoloration, damage, or heat stress. • Inspect wire insulation and shielding for wear. • Repair or replace damaged wiring. Terminals • Inspect terminals for stripped, damaged, or loose connections. • Tighten loose screws and replace damaged screws or terminals. Relays and Contactors • Inspect contactors and relays for excessive noise during operation. • Inspect coils for signs of overheating such as melted or cracked insulation.

• Check coil voltage for over or under voltage conditions. • Replace damaged removable relays contactors or circuit board.