6.3 Periodic Maintenance Table 6.4 Performance Life Monitors Used for Component Replacement ■ Related Drive Parameters Table 6.5 Maintenance Parameter Settings NOTICE: After replacing parts, reset the appropriate maintenance parameters (o4-03, o4-05, o4-07, and o4- 09) to 0. If these parameters are not reset, the function will continue to count down the performance life of the new replaced components. OYMC TOEP C71060622-01-OY V1000 User Manual 249 Parameter Component Contents U4-03 Cooling Fan Displays the accumulated operation time of the cooling fan, from 0 to 99999 hours. This value is automatically reset to 0 once it reaches 99999.

U4-04 Displays the accumulated cooling fan operation time as a percentage of the specified maintenance period (displayed in percent%). U4-05 Main Circuit (DC bus) Electrolytic Capacitors Displays the accumulated time the capacitors are used as a percentage of the specified maintenance period. U4-06 Inrush (pre-charge) relay Displays the number of times the drive is powered up as a percentage of the performance life of the inrush circuit. U4-07 IGBT Displays the percentage of the maintenance period reached by the IGBTs.

Parameter Parameter Name Control Mode Operator Display V/f Open Loop Vector Open Loop Vector for PM o4-03 Cooling Fan Maintenance Setting (Operation Time) A A A o4-05 Capacitor Maintenance Setting A A A 6 o4-07 Inrush Prevention Relay (pre-charge) Maintenance Setting A A A o4-09 IGBT Maintenance Setting A A A