omron — 7.1 Section Safety

7.1 Section Safety WARNING Do not touch any terminals before the capacitors have fully discharged. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level. Failure to comply could result in death or serious injury. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury.

Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives. Peripheral Devices & Options Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing and wear eye protection before beginning work on the drive. 7 Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. OYMC TOEP C71060622-01-OY V1000 User Manual 261