7.4 Installing Peripheral Devices 7.4 Installing Peripheral Devices This section describes the proper steps and precautions to take when installing or connecting various peripheral devices to the drive. • Refer to peripheral device manual for detailed installation instructions. NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral devices could result in drive performance degradation due to improper power supply. ◆ Installing a Molded Case Circuit Breaker (MCCB) Install a MCCB for line protection between the power supply and the main circuit power supply input terminals R/L1, S/L2 and T/L3.

This protects the main circuit and devices wired to the main circuit while also providing overload protection. Consider the following when selecting and installing a MCCB: • The capacity of the MCCB should be 1.5 to 2 times the rated output current of the drive. Use an MCCB keep the drive from faulting out instead of using overheat protection (150% for one minute at the rated output current). • If several drives are connected to one MCCB or an MCCB is shared with other equipment, use a sequence that shuts the power OFF when errors are output by using magnetic contactor (MC) as shown the following figure.

Peripheral Devices & Options Figure 7.2 Drive MCCB MC 7 S/L2 T/L3 R/L1 Three-Phase AC200 㨪 240 V 50/60 Hz Single-Phase AC200 㨪 240 V 50/60 Hz MC MB SA MC Figure 7.2 Example for Connecting an MCCB MC WARNING! Electrical Shock Hazard. Disconnect the MCCB and MC before wiring terminals. Failure to comply may result in serious injury or death. OYMC TOEP C71060622-01-OY V1000 User Manual 265