7.4 Installing Peripheral Devices ◆ Installing a Leakage Breaker Drive outputs generate high-frequency leakage current as a result of high-speed switching. Install a Ground Fault Circuit Interrupter (GFCI) on the input side of the drive to switch off potentially harmful leakage current. Factors in determining leakage current: • Size of the AC drive • AC drive carrier frequency • Motor cable type and length • EMI/RFI filter In order to safely protect the drive system, select a breaker that senses all types of current (AC and DC) and high frequency currents Note: Choose a GFCI designed specifically for an AC drive.
The operation time should be at least 0.1 second with sensitivity amperage of at least 200 mA per drive. The output waveform of the drive may cause the leakage current to increase. This may, in turn, cause the leakage breaker to malfunction. Take the following steps to correct the problem: • Increase the sensitivity amperage. • Lower the carrier frequency. ◆ Installing a Magnetic Contactor ■ Disconnecting the Power Supply The drive can be shut off in the case of a fault in external equipment such as braking resistors through use of a Magnetic Contactor (MC). NOTICE: Install the MC on the input side of the drive when the drive should not automatically restart after power loss.
To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the MC more than once every 30 minutes. Frequent use can damage the drive. Use the drive to stop and start the motor. ■ Protecting the Braking Resistor or Braking Resistor Unit Use an MC on the input side of the drive to protect a braking resistor or braking resistor unit from overheat or fire. WARNING! Fire Hazard. When using a braking unit, use a thermal relay on the braking resistors and configure a fault contact output for the braking resistor unit to disconnect drive main power via an input contactor.
Inadequate braking circuit protection could result in death or serious injury by fire from overheating resistors. ◆ Connecting an AC or DC Reactor AC and DC reactors suppress surges in current and improve the power factor on the input side of the drive. 266 OYMC TOEP C71060622-01-OY V1000 User Manual