7.4 Installing Peripheral Devices Use a DC reactor or AC reactor or both: • To suppress harmonic current or improve the power factor of the power supply. • When using an advancing capacitor switch. • With a large capacity power supply transformer (over 600 kVA). Note: Use an AC or DC reactor when also connecting a thyristor converter (such as a DC drive) to the same power supply system, regardless of the conditions of the power supply.
■ Connecting an AC Reactor Figure 7.3 A – Power supply C – AC reactor B – MCCB D – Drive Peripheral Devices & Options ■ Connecting a DC Reactor Figure 7.3 Connecting an AC Reactor Ensure the jumper between terminals +1 and +2 (terminals are jumpered for shipment) is removed when connecting a DC reactor. The jumper must be installed if no DC reactor is used. Refer to Figure 7.4 for an example of DC reactor wiring. 7 Figure 7.4 C A B R/L1 S/L2 T/L3 D A – Power supply C – Drive B – MCCB D – DC reactor Figure 7.4 Connecting a DC Reactor OYMC TOEP C71060622-01-OY V1000 User Manual 267 C D A B U X R/L1 V Y S/L2 W Z T/L3 Y S/L2 Z T/L3 +2