omron — A.2 Single/Three-Phase 200 V Class Drive

A.2 Single/Three-Phase 200 V Class Drive A.2 Single/Three-Phase 200 V Class Drive Table A.2 Power Ratings Drives with a single-phase power supply input will output three-phase power, and cannot run a single-phase motor. This drive does not have a Normal Duty rating. The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance. Rated motor capacity is calculated with a rated output voltage of 220 V. Carrier frequency is set to 10 kHz.

Current derating is required in order to raise the carrier frequency. Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency. Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency. OYMC TOEP C71060622-01-OY V1000 User Manual 281 Item Specification Three-Phase: VZA 20P1 20P2 20P4 20P7 21P5 22P2 24P0 Single-Phase:

VZA B0P1 B0P2 B0P4 B0P7 B1P5 B2P2 B4P0 Maximum Motor Size Allowed (kW) HD Rating 0.1 0.2 0.4 0.75 1.5 2.2 4.0 ND Rating 0.2 0.4 0.75 1.1 2.2 3.0 5.5 Input Input Current (A) Three- Phase HD Rating 0.7 1.5 2.9 5.8 7.5 11.0 18.9 ND Rating 1.1 1.9 3.9 7.3 10.8 13.9 24.0 Single- Phase HD Rating 1.4 2.8 5.5 11.0 14.1 20.6 35.0 ND Rating 2.0 3.6 7.3 13.8 20.2 24.0 – Output Rated Output Capacity (kVA) HD Rating 0.3 0.6 1.1 1.9 3.0 4.2 6.7 ND Rating 0.5 0.7 1.3 2.3 3.7 4.6 7.5 Output Current (A) HD Rating 0.8 1.6 3.0 5.0 8.0 11.0 17.5 ND Rating 1.2 1.9 3.5 (3.3) 6.0 9.6 12.0 19.6 Overload Tolerance ND Rating: 120% of rated output current for 1 minute HD Rating:

150% of rated output current for 1 minute (Derating may be required for applications that start and stop frequently) Carrier Frequency User adjustable between 2 and 15 kHz (see HD output current line of this table for default values) Max Output Voltage (V) Three-phase 200 to 240 V (proportional to input voltage) Max Output Frequency (Hz) 400 Hz (user-adjustable) Power Supply Rated Voltage Rated Frequency Three-phase power: Three-phase 200 to 240 V 50/60 Hz Single-phase power: 200 to 240 V 50/60 Hz A Allowable Voltage Fluctuation -15 to 10% Allowable Frequency Fluctuation ±5% Harmonic Countermeasures DC Reactor Optional