omron — A.2 Single/Three-Phase 200 V Class Drive

A.2 Single/Three-Phase 200 V Class Drive Table A.3 Power Ratings Continued Drives with a single-phase power supply input will output three-phase power, and cannot run a single-phase motor. The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance. Rated motor capacity is calculated with a rated output voltage of 220 V. Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.

Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency. Note: Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated input and output current, overload capacity, carrier frequency and current limit. Set parameter C6-01 to “0” (default) for HD or “1” for ND. 282 OYMC TOEP C71060622-01-OY V1000 User Manual Item Specification Three-Phase: VZA 25P5 27P5 2011 2015 Single-Phase:

VZA - - - - Maximum Motor Size Allowed (kW) HD Rating 5.5 7.5 11.0 15.0 ND Rating 7.5 11.0 15.0 18.5 Input Input Current (A) Three-Phase HD Rating 26.0 35.4 51.9 70.8 ND Rating 34.7 50.9 69.4 85.6 Single-Phase HD Rating - - - - ND Rating - - - - Output Rated Output Capacity (kVA) HD Rating 9.5 12.6 17.9 22.9 ND Rating 11.4 15.2 21.3 26.3 Output Current (A) HD Rating 25.0 33.0 47.0 60.0 ND Rating 30.0 40.0 56.0 69.0 Overload Tolerance ND Rating: 120% of rated output current for 1 minute HD Rating:

150% of rated output current for 1 minute (Derating may be required for applications that start and stop frequently) Carrier Frequency User adjustable between 2 and 15 kHz (see HD output current line of this table for default values) Max Output Voltage (V) Three-phase 200 to 240 V (proportional to input voltage) Max Output Frequency (Hz) 400 Hz (user-adjustable) Power Supply Rated Voltage Rated Frequency Three-phase power: Three-phase 200 to 240 V 50/60 Hz Single-phase power: 200 to 240 V 50/60 Hz Allowable Voltage Fluctuation -15 to 10% Allowable Frequency Fluctuation ±5% Harmonic Countermeasures DC Reactor Optional