A.3 Three-Phase 400 V Class Drives A.3 Three-Phase 400 V Class Drives Table A.4 Power Ratings Specifications A The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. .Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and power supply impedance. Rated motor capacity is calculated with a rated output voltage of 440 V. Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency. Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
OYMC TOEP C71060622-01-OY V1000 User Manual 283 Item Specification VZA 40P2 40P4 40P7 41P5 42P2 43P0 44P0 Maximum Applicable Motor Capacity (kW) HD Rating 0.2 0.4 0.75 1.5 2.2 3.0 3.7 ND Rating 0.4 0.75 1.5 2.2 3.0 3.7 5.5 Input Input Current (A) HD Rating 1.2 1.8 3.2 4.4 6.0 8.2 10.4 ND Rating 1.2 2.1 4.3 5.9 8.1 9.4 14.0 Output Output Current (kVA) HD Rating 0.9 1.4 2.6 3.7 4.2 5.5 7.0 ND Rating 0.9 1.6 3.1 4.1 5.3 6.7 8.5 Output Current (A) HD Rating 1.2 1.8 3.4 4.8 5.5 7.2 9.2 ND Rating 1.2 2.1 4.1 5.4 6.9 8.8 11.1 Overload Tolerance ND Rating: 120% of rated output current for 60 s HD Rating:
150% of rated output current for 60 s (Derating may be required for applications that start and stop frequently) Carrier Frequency User adjustable between 2 and 15 kHz (see HD output current line of this table for default values) Maximum Output Voltage (V) Three-phase: 380 to 480 V (proportional to input voltage) Maximum Output Frequency (Hz) 400 Hz (user-adjustable) Power Supply Rated Voltage Rated Frequency Three-phase: 380 to 480 V 50/60 Hz Allowable Voltage Fluctuation -15 to 10% Allowable Frequency Fluctuation ±5% Harmonic Countermeasures DC Reactor Optional