A.3 Three-Phase 400 V Class Drives Table A.5 Power Ratings Continued The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. .Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and power supply impedance. Rated motor capacity is calculated with a rated output voltage of 440 V. Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency. Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency. Note:
Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated input and output current, overload capacity, carrier frequency and current limit. Set parameter C6-01 to “0” (default) for HD or “1” for ND.
284 OYMC TOEP C71060622-01-OY V1000 User Manual Item Specification VZA 45P5 47P5 4011 4015 Maximum Applicable Motor Capacity (kW) HD Rating 5.5 7.5 11.0 15.0 ND Rating 7.5 11.0 15.0 18.5 Input Input Current (A) HD Rating 15.0 20.0 29.0 39.0 ND Rating 20.0 24.0 38.0 44.0 Output Output Current (kVA) HD Rating 11.3 13.7 18.3 23.6 ND Rating 13.3 17.5 23.6 29.0 Output Current (A) HD Rating 14.8 18.0 24.0 31.0 ND Rating 17.5 23.0 31.0 38.0 Overload Tolerance ND Rating: 120% of rated output current for 60 s HD Rating:
150% of rated output current for 60 s (Derating may be required for applications that start and stop frequently) Carrier Frequency User adjustable between 2 and 15 kHz (see HD output current line of this table for default values) Maximum Output Voltage (V) Three-phase: 380 to 480 V (proportional to input voltage) Maximum Output Frequency (Hz) 400 Hz (user-adjustable) Power Supply Rated Voltage Rated Frequency Three-phase: 380 to 480 V 50/60 Hz Allowable Voltage Fluctuation -15 to 10% Allowable Frequency Fluctuation ±5% Harmonic Countermeasures DC Reactor Optional