A.6 Drive Derating Data A.6 Drive Derating Data The drive can be operated at above rated temperature, altitude and default carrier frequency by derating the drive capacity. For example, a 10 amp continuous rated drive may be operated at higher temperatures if it is only used to supply 8 amps continuous. ◆ Carrier Frequency Derating As the carrier frequency of the drive is increased above the factory setting the drive capacity should be derated according to Figure A.1 . Figure A.1 Drive Rating Carrier Frequency Derating 0& 200 V Class:
80% of HD *& 400 V Class 60% of HD Carrier(C6-02) Figure A.1 Carrier Frequency Derating ◆ Temperature Derating As the ambient temperature for the drive is increased above the drive specification the drive should be derated. Additionally parameter L8-35 Installation Method Selection on page 290 should be set according to enclosure type and mounting method as illustrated in Figure A.2 Ambient Temperature and Installation Method Derating on page 291 .
■ Output Current Derating Due to Ambient Temperature If the ambient temperature is above the drive specification or if drives are side-by-side mounted in a cabinet, the parameters L8-12 and L8-35 must be set according to the installation conditions. The output current is derated as shown in Figure A.2 . 290 OYMC TOEP C71060622-01-OY V1000 User Manual