A.6 Drive Derating Data Figure A.2 Parameter L8-35 = 0 (IP20) Parameter L8-35 = 2 (IP20/NEMA Type 1) Drive Rating Parameter L8-35 = 3 (Finless/ Fin outside installation) Parameter L8-35 = 1 (Side-by-side installation) o o o o Ambient temp C Parameter L8-12 o Specifications Figure A.2 Ambient Temperature and Installation Method Derating ◆ Altitude Derating A The drives standard ratings are valid for an installation altitude up to 1000 m. If the altitude exceeds 1000m both, the drive input voltage and the rated output current must be derated for 1 % per 100 m. The maximum altitude is 3000 m. OYMC TOEP C71060622-01-OY V1000 User Manual 291 No.
Name Description Range Def. L8-12 Ambient Temperature Setting Adjust the drive overload (OL2) protection level when the drive is installed in an environment that exceeds its ambient temperature rating. 40 to 60 40 °C L8-35 Installation Method Selection 0: Disabled (standard installation) 1: Side-by-Side installation 2: IP20/NEMA Type 1 3: Finless/Fin Outside installation 0 to 3 0