B.2 Parameter Table B.2 Parameter Table The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor Control Method, Password, User Parameters and more. ◆ A: Initialization Parameters OYMC TOEP C71060622-01-OY V1000 User Manual 295 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M A1: Initialization Parameters Use A1 parameters to configure the basic environment for drive operation. A1-01 Access Level Selection Selects which parameters are accessible via the digital operator. 0: Operation only 1: User Parameters (access to a set of parameters selected by the user) 2:

Advanced Access Level 0 to 2 2 A A A 101H — A1-02 Control Method Selection Selects the Control Method of the drive. 0: V/f Control without PG 2: Open Loop Vector (OLV) 5: PM Open Loop Vector (PM) Note: Does not return to the default setting when the drive is initialized. 0, 2, 5 0 S S S 102 118 A1-03 Initialize Parameters Resets all parameters to factory default settings. (Initializes the drive then returns A1-03 to 0) 0: No Initialize 1110: User Initialize (First set user parameter values must be stored using parameter o2-03) 2220: 2-Wire Initialization 3330: 3-Wire Initialization 5550:

OPE04 Error Reset 0 to 3330 0 A A A 103 — The following parameters are not reset when the performing initialization: A1-00, A1-02, A1-07, and all U2 and U3 monitors. B A1-04 Password 1 When the value set into A1-04 does not match the value set into A1-05, parameters A1-01 thru A1-03, A1-06, and A2-01 thru A2-32 cannot be changed. 0 to 9999 0 A A A 104 — A1-05 Password 2 0 to 9999 0 A A A 105 — This parameter is hidden from view. To access A1-05, first display A1-04. Then press the STOP key while holding down the up arrow key. Parameter A1-05 will appear. —