B.2 Parameter Table Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 does not = 0. Default setting value is dependent on parameter A1-06, Application Selection. Parameter can be changed during run. ◆ b: Application Application parameters configure the Run Command Source, DC Injection Braking, Speed Search, Timer functions, PID control, the Dwell function, Energy Savings and a variety of other application-related settings. 296 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg.
V/f O LV P M A1-06 Application Preset Sets parameters that are commonly used in certain applications to A2-01 through A2-16 for easier access. 0: General-purpose (A2 parameters are not affected) 1: Water supply pump 2: Conveyor 3: Exhaust fan 4: HVAC fan 5: Air compressor 6: Hoist 7: Travelling 0 to 7 0 A A A 127 — A1-07 FBD’s Function Selection 0: Disabled 1: Enabled 2: Multi-function input (enabled when H1- = 9F) 0 to 2 0 A A A — A2: User Parameters Use A2 parameters to program the drive. A2-01 to A2-32 User Parameters, 1 to 32 Parameters that were recently edited are listed here. The user can also select parameters to appear here for quick access.
Parameters will be stored here for quick access when A1-01 = 1. b1-01 to o2-08 -- A A A 106 to 125 — A2-33 User Parameter Automatic Selection 0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters. 1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-17 through A2-32 for quick access. 0,1 1 A A A 126 —