B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 297 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M b1: Operation Mode Selection Use b1 parameters to configure the operation mode. b1-01 Frequency Reference Selection 1 Selects the frequency reference input source. 0: Operator - Digital preset speed d1-01 to d1- 17. 1: Terminals - Analog input terminal A1 or A2. 2: Memobus communications 3: Option PCB 4: Pulse Input (Terminal RP) 0 to 4 1 S S S 180 120 b1-02 Run Command Selection 1 Selects the run command input source. 0: Operator - RUN and STOP keys on the digital operator. 1: Digital input terminals S1 to S6 2:
Memobus communications 3: Option PCB. 0 to 3 1 S S S 181 123 b1-03 Stopping Method Selection Selects the stopping method when the run command is removed. 0: Ramp to Stop 1: Coast to Stop 2: DC Injection Braking to Stop 3: Coast with Timer (A new run command is ignored if received before the timer expires) 9: Simple Positioning 0 to 3, 9 0 S S S 182 125 DC Injection Braking at Stop cannot be selected when using Open Loop Vector for PM motors. b1-04 Reverse Operation Selection Permits or prohibits reverse operation. 0: Reverse enabled. 1: Reverse disabled.
0,1 0 A A A 183 — b1-07 Local/Remote Run Selection Determines the operation when the Run command source is switched from LOCAL to REMOTE or between Run source 1 and 2 while an external Run command is active at the new source. 0: External Run command has to be cycled at the new source to be activated. 1: External Run command at new source is accepted immediately. 0,1 0 A A A 186 — b1-08 Run Command Selection while in Programming Mode 0: Run command accepted only in the operation menu. 1: Run command accepted in all menus. 2: Prohibit entering programming mode during Run 0 to 2 0 A A A 187 —