B.2 Parameter Table 298 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M b1-14 Phase Order Selection Sets the phase order for drive output terminals U/T1, V/T2 and W/T3. 0: Standard 1: Switch phase order 0,1 0 A A A 1C3 — b1-15 Frequency Reference 2 Selects the frequency reference input source. 0: Operator - Digital preset speed d1-01 to d1- 17. 1: Terminals - Analog input terminal A1 or A2 2: Memobus communications 3: Option PCB 4: Pulse Input (Terminal RP) 0 to 4 0 A A A 1C4 — b1-16 Run Command Source 2 Selects the run command input source. 0: Operator - RUN and STOP keys on the digital operator. 1:
Digital input terminals S1 to S6 2: Memobus communications 3: Option PCB 0 to 3 0 A A A 1C5 — b1-17 Run Command at Power Up Determines the operation when a Run command is active at power up of the drive. 0: Run command not issued, needs to be cycled 1: Run command issued, motor operation start 0,1 0 A A A 1C6 — b2: DC Injection Braking Use b2 parameters to configure DC Injection Braking operation b2-01 DC Injection Braking Start Frequency Sets the frequency at which DC Injection Braking starts when Ramp to Stop (b1-03 = 0) is selected. If b2-01 0.0 to 10.0 0.5 Hz A A A 189 — b2-02 DC Injection Braking Current Sets the DC Injection Braking current as a percentage of the drive rated current.
0 to 75 50% A A − 18A — b2-03 DC Injection Braking Time/DC Excitation Time at Start Sets DC Injection Braking time at start. Disabled when set to 0.00 seconds. 0.00 to 10.00 0.00 s A A − 18B — b2-04 DC Injection Braking Time at Stop Sets DC Injection Braking time at stop.When b1-03 = 2, actual DC Injection time is calculated as follows: (b2-04) x 10 x (Output Freq) / (E1-04). When b1-03 = 0, this parameter sets the amount of DC Injection time applied to the motor at the end of the decel ramp or High Slip Braking. Disabled when set to 0.00.
0.00 to 10.00 0.50 s A A − 18C — b2-08 Magnetic Flux Compensation Capacity Sets the magnetic flux compensation as a percentage of the no-load current value (E2-03). 0 to 1000 0% − A − 190 —