omron — b: Application

B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 299 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M b2-12 Short Circuit Brake Time at Start Sets the time for Short-Circuit Brake operation at start. Disabled when set to 0.00. 0.00 to 25.50 0.00 s − − A 1BA — b2-13 Short Circuit Brake Time at Stop Sets Short-Circuit Brake operation time at stop. Used to stop a motor rotating due to inertia. Disabled when set to 0.00 seconds. 0.00 to 25.50 0.50 s − − A 1BB — b3: Speed Search Use B3 parameters to configure Speed Search function operation. b3-01 Speed Search Selection Enables/disables speed search function at start. 0:

Disabled - Speed Search is not automatically performed at start. 1: Enabled - Speed Search is automatically performed at start. 0 to 1 0 A A A 191 — b3-02 Speed Search Deactivation Current Sets the current level at which the speed is assumed to be detected and Speed Search is ended. Set in percent of the drive rated current. 0 to 200 120 A A − 192 — b3-03 Speed Search Deceleration Time Sets the time constant used to reduce the output frequency during speed search. Related to a change from max. output frequency to 0.

0.1 to 10.0 2.0 s A A − 193 — b3-05 Speed Search Delay Time Delays the speed search operation after a momentary power loss to allow time for an external output contactor to close. 0.0 to 100 0.2 s A A A 195 — b3-06 Output Current 1 during Speed Search Sets the current injected to the motor at the beginning of Estimation type Speed Search. Set as a factor to the motor rated current. 0.0 to 2.0 A A − 196 — b3-10 Speed Search Detection Compensation Gain Sets the gain which is applied to the speed detected by Speed Estimation Speed Search before the motor is reaccelerated.Increase this setting if OV occurs when performing speed search.

1.00 to 1.20 1.05 A A − 19A — b3-14 Bi-Directional Speed Search Selection Selects if Speed Search detects the motor rotation direction during speed search. 0: Disabled–Frequency reference direction used 1: Enabled–Detected direction used 0,1 0 A A − 19E — b3-17 Speed Search Restart Current Level Sets the speed search restart current level in percentage of the drive rated current. 0 to 200 150 % A A − 1F0 — b3-18 Speed Search Restart Detection Time Sets the time in seconds for speed search restart to be detected. 0.00 to 1.00 0.10 s A A − 1F1 — b3-19 Number of Speed Search Restarts Sets the number of restarts possible for speed search restart operations. 0 to 10 3 A A − 1F2 —