omron — b: Application

B.2 Parameter Table 300 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M b3-24 Speed Search Method Selection Sets the Speed Search detection mode. 0: Current Detection Type 1: Speed Estimation Type 0,1 0 A A − 1C0 — b3-25 Speed Search Retry Interval Time Sets the wait time before Speed Search restarts. 0 to 30.0 0.5 s A A A 1C8 — b4: Timer Function Use b4 parameters to configure timer function operation. b4-01 Timer Function On-Delay Time Used in conjunction with a multi-function digital input (H1- = 18) and a multi- function digital output (H2- = 12) programmed for the timer function.

This sets the amount of time between digital input closure and digital output activation. 0.0 to 300.0 0.0 s A A A 1A3 — b4-02 Timer Function Off-Delay Time Used in conjunction with a multi-function digital input (H1- = 18) and a multi- function digital output programmed for the timer function. This sets the amount of time the output remains activated after the digital input is opened. 0.0 to 300.0 0.0 s A A A 1A4 — b5: PID Control Use b5 parameters to configure the PID control drive function. b5-01 PID Function Setting Sets the PID control mode. 0: Disabled 1: Enable (Deviation is D-controlled) 2: Enable (Feedback is D-controlled) 3:

Enable (Deviation is D-controlled, PID output added to Freq. Ref.) 4: Enable (Feedback is D-controlled, PID output added to Freq. Ref.) 0 to 4 0 A A A 1A5 — b5-02 Proportional Gain Setting (P) Sets the proportional gain of the PID controller. A setting of 0.00 disables P control. 0.00 to 25.00 1.00 A A A 1A6 — b5-03 Integral Time Setting (I) Sets the integral time for the PID controller. A setting of 0.0 s disables integral control. 0.0 to 360.0 1.0 s A A A 1A7 — b5-04 Integral Limit Setting Sets the maximum output possible from the integrator. 0.0 to 100.0 100.0 % A A A 1A8 — b5-05 Derivative Time (D) Sets D control derivative time. A setting of 0.00 s disables derivative control.

0.00 to 10.00 0.00 s A A A 1A9 — b5-06 PID Output Limit Sets the maximum output possible from the entire PID controller. 0.0 to 100.0 100.0 % A A A 1AA — b5-07 PID Offset Adjustment Applies an offset to the PID controller output. -100.0 to +100.0 0.0% A A A 1AB —