B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 301 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M b5-08 PID Primary Delay Time Constant Sets the amount of time for the filter on the output of the PID controller. 0.00 to 10.00 0.00 s A A A 1AC — b5-09 PID Output Level Selection Sets the PID controller output direction. 0: Normal Output (direct acting) 1: Reverse Output (reverse acting) 0,1 0 A A A 1AD — b5-10 PID Output Gain Setting Sets the gain applied to the PID output. 0.00 to 25.00 1.00 A A A 1AE — b5-11 PID Output Reverse Selection Sets the drive operation with negative PID output. 0: Drive stops with negative PID output 1:
Rotation direction reverses with negative PID output. When using setting 1 make sure, reverse operation is permitted by parameter b1-04. 0,1 0 A A A 1AF — b5-12 PID Feedback Reference Missing Detection Selection Configures the PID feedback loss detection. 0: Disabled. 1: Feedback loss detected when PID enabled. Alarm output, operation is continued without triggering a fault contact. 2: Feedback loss detected when PID enabled. Fault output, operation is stopped and a fault contact is triggered. 3: Feedback loss detection even when PID is disabled by digital input. No alarm/fault output. “PID feedback loss” digital output is switched, 4:
PID Feedback error detection even when PID is disabled by digital input. An alarm is triggered and the drive continues to run. 5: PID Feedback error detection even when PID is disabled by digital input. Fault is triggered and output is shut off. 0 to 5 0 A A A 1B0 — b5-13 PID Feedback Loss Detection Level Sets the PID feedback loss detection level. 0 to 100 0% A A A 1B1 — b5-14 PID Feedback Loss Detection Time Sets the PID feedback loss detection delay time in terms of seconds. 0.0 to 25.5 1.0 s A A A 1B2 — b5-15 PID Sleep Function Start Level Sets the sleep function start frequency. Note: Also enabled when PID is not active.
0.0 to 400.0 0.0 Hz A A A 1B3 — b5-16 PID Sleep Delay Time Sets the sleep function delay time in units of 0.1 seconds. 0.0 to 25.5 0.0 s A A A 1B4 — b5-17 PID Accel/Decel Time Applies an accel/decel time to the PID setpoint reference. 0 to 255 0 s A A A 1B5 —