B.2 Parameter Table 302 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M b5-18 PID Setpoint Selection Selects b5-19 as PID setpoint value. 0: Disabled 1: Enabled, b5-19 becomes PID target 0,1 0 A A A 1DC — b5-19 PID Setpoint Value Sets the PID target value when b5-18 = 1. 0.00 to 100.00 0.00 % A A A 1DD — b5-20 PID Setpoint Scaling Sets the units for b5-19, and for parameter monitors U5-01 (PID Feedback) and U5-04 (PID Setpoint). 0: 0.01Hz units 1: 0.01% units (100% = max output frequency) 2: r/min (motor pole number must be set up) 3:
User-set (set to b5-38 and b5-39) 0 to 3 1 A A A 1E2 — b5-34 PID Output Lower Limit Sets the minimum output possible from the PID controller. -100.0 to +100.0 0.00 % A A A 19F — b5-35 PID Input Limit Limits the PID control input (deviation signal). Acts as a bipolar limit. 0 to 1000.0 1000. 0% A A A 1A0 — b5-36 PID Feedback High Detection Level Sets the PID feedback high detection level. 0 to 100 100 % A A A 1A1 — b5-37 PID Feedback High Level Detection Time Sets the PID feedback high level detection delay time. 0.0 to 25.5 1.0 s A A A 1A2 — b5-38 PID Setpoint / User Display 0 to 60000: User-Set Display if b5-20=3 Set the numbers displayed by designating the maximum PID target.
1 to 60000 A A A 1FE — b5-39 PID Setpoint Display Digits Sets the number of digits the PID setpoint. 0: No decimal places 1: One decimal places 2: Two decimal places 3: Three decimal places 0 to 3 A A A 1FF —