omron — b: Application

B.2 Parameter Table Parameter List B Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 2-OLV control. Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control. Default setting is dependent on parameter b5-20, PID Setpoint Scaling. Default setting value is dependent on parameter o2-04, Drive Unit Selection. Default setting value is dependent on parameter o2-09, Initialization Spec. Selection. OYMC TOEP C71060622-01-OY V1000 User Manual 303 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M b6:

Dwell Function Use b6 parameters to configure dwell function operation. b6-01 Dwell Reference at Start The Dwell function is used to temporarily hold the frequency when driving a motor with a heavy load. Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain that frequency at start. Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain that frequency at stop. 0.0 to 400.0 0.0 Hz A A A 1B6 — b6-02 Dwell Time at Start 0.0 to 10.0 0.0 s A A A 1B7 — b6-03 Dwell Frequency at Stop 0.0 to 400.0 0.0 Hz A A A 1B8 — b6-04 Dwell Time at Stop 0.0 to 10.0 0.0 s A A A 1B9 — Output Frequency Run command 10 Time b8:

Energy Saving Use b8 parameters to configure the energy saving/conservation drive function. b8-01 Energy Saving Control Selection Selects the Energy Savings function. 0: Disabled 1: Enabled (set b8-04) 0,1 0 A A − 1CC — b8-02 Energy Saving Gain Sets energy savings control gain when in Open Loop Vector (OLV) control mode. 0.0 to 10.0 0.7 − A − 1CD — b8-03 Energy Saving Control Filter Time Constant Sets energy saving control filter time constant when in Open Loop Vector control. 0.00 to 10.00 0.50 − A − 1CE — b8-04 Energy Saving Coefficient Value Sets the Energy Saving coefficient and is used to fine adjustments in V/f Control.

0.0 to 655.00 A − − 1CF — b8-05 Power Detection Filter Time Sets a filter time for the Power Detection used by Energy Savings in V/f Control. 0 to 2000 20 ms A − − 1D0 — b8-06 Search Operation Voltage Limit Sets the limit for the voltage search operation performed by Energy Savings in V/f Control. Set as a percentage of the motor base voltage. Disabled when set to 0%. 0 to 100 0% A − − 1D1 —