B.2 Parameter Table 306 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M C3-03 Slip Compensation Limit Sets the slip compensation upper limit. Set as a percentage of motor rated slip (E2-02). Disabled when Simple V/f Control with PG (H6-01 = 3) is used. 0 to 250 200% A A − 211 — C3-04 Slip Compensation Selection during Regeneration Selects slip compensation during regenerative operation. 0: Disabled 1: Enabled Using the Slip Compensation function during regeneration may require a braking option to handle momentary increasing regenerative energy.

0,1 0 A A − 212 — C3-05 Output Voltage Limit Operation Selection Selects if the motor magnetic flux is reduced during output voltage saturation. 0: Disabled 1: Enabled 0,1 0 − A − 213 — C4: Torque Compensation Use C4 parameters to configure Torque Compensation function. C4-01 Torque Compensation Gain V/f control: Sets the gain for the automatic torque (voltage) boost function and helps to produce better starting torque. Increase this setting when using a long motor cable or when the motor is significantly smaller than the drive capacity. Decrease this setting when motor oscillation occurs. Set the value so that the current at low speed does not exceeds the drives rated current.

Open Loop Vector: Sets the torque compensation function gain. Normally no change is required. 0.00 to 2.50 1.00 A A A 215 — C4-02 Torque Compensation Primary Delay Time Sets the torque compensation filter time. Increase this setting when motor oscillation occurs. Reduce the setting if there is not enough response from the motor. 0 to 60000 200 ms A A A 216 — C4-03 Torque Compensation at Forward Start Sets torque compensation at forward start as a percentage of motor torque. 0.0 to 200.0 0.0% − A − 217 — C4-04 Torque Compensation at Reverse Start Sets torque compensation at reverse start as a percentage of motor torque. -200.0 to 0.0 0.0% − A − 218 —