B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 307 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M C4-05 Torque Compensation Time Constant Sets the time constant for torque compensation at forward start and reverse start (C4-03 and C4-04). The filter is disabled if the time is set to 4 ms or less. 0 to 200 10 ms – A – 219 — C4-06 Torque Compensation Primary Delay Time 2 Sets the torque compensation time 2. When an OV fault occurs with sudden load changes or at the and of an acceleration, increase the setting. Note: Adjustment is not normally required. If adjusted then AFR time 2 (n2-03) should be adjusted too.
0 to 10000 150 ms – A – 21AH — C5: Speed Control (ASR) Use C5 parameters to configure the Automatic Speed Regulator (ASR). C5 parameters are available only when using V/f with Simple PG (H6-01 = 3). C5-01 ASR Proportional Gain 1 Sets the proportional gain of the speed control loop (ASR). 0.00 to 300.00 0.20 A – – 21B — C5-02 ASR Integral Time 1 Sets the integral time of the speed control loop (ASR). 0.000 to 10.000 0.200 A 21C — C5-03 ASR Proportional Gain 2 Sets the speed control gain 2 of the speed control loop (ASR). 0.00 to 300.00 0.02 A − − 21D — C5-04 ASR Integral Time 2 Sets the integral time 2 of the speed control loop (ASR).
0.000 to 10.000 0.050 s A – – 21E — C5-05 ASR Limit Sets the upper limit for the speed control loop (ASR) as a percentage of the maximum output frequency (E1-04). 0.0 to 20.0 5.0% A 21F — C6: Carrier Frequency Use C6 parameters to configure the carrier frequency drive settings. C6-01 Normal/Heavy Duty Selection Selects the load rating for the drive. 0: Heavy Duty (HD) for constant torque applications. 1: Normal Duty (ND) for variable torque applications. This setting affects the Rated output current and overload tolerance of the drive. 0,1 0 S S S 223 130