omron — C: Tuning

B.2 Parameter Table Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 2-OLV control. Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control. Default setting value is dependent on parameters o2-04, Drive Unit Selection, A1-02, Control Method Selection and C6-01, Normal/Heavy Duty selection. Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range becomes 0.00 to 600.00 seconds. Default setting value is dependent on parameter C6-02, Carrier Frequency Selection.

Parameter can be changed during run. 308 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M C6-02 Carrier Frequency Selection Selects the carrier frequency 1: 2.0 kHz 2: 5.0 kHz 3: 8.0 kHz 4: 10.0 kHz 5: 12.5 kHz 6: 15.0 kHz 7: Swing PWM1 (Audible sound 1) 8: Swing PWM2 (Audible sound 2) 9: Swing PWM3 (Audible sound 3) A: Swing PWM4 (Audible sound 4) B to E: No setting possible F: User defined (determined by C6-03 through C6-05) 1 to F S S S 224 131 C6-03 Carrier Frequency Upper Limit Open Loop Vector: C6-03 defines the fixed carrier frequency if C6-02 = F. V/f control:

C6-03 and C6-04 set upper and lower limits for the carrier frequency. 1.0 to 15.0 A A A 225 — C6-04 Carrier Frequency Lower Limit 0.4 to 15.0 A - - 226 — carrier frequency C6-03 C6-04 output frequency × (C6-05) × K output frequency E1-04 max output frequency The coefficient K depends on C6-03: C6-03 ≥ 10.0 kHz: K = 3 10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2 5.0 kHz > C6-03: K = 1 When C6-05 ≤ 6, C6-04 is disabled (makes the carrier frequency C6-03 value). C6-05 Carrier Frequency Proportional Gain Sets the relationship of output frequency to carrier frequency when C6-02 = F. 00 to 99 A - - 227 —