B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 317 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f OL V PM E3-04 Motor 2 Max Output Frequency These parameters set the V/f pattern for motor 2. To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the four frequencies are set according to these rules or OPE10 fault will occur: E3-04 ≥ E3-06 > E3-07 > E3-09 40.0 to 400.0 50 Hz A A − 31A — E3-05 Motor 2 Max Voltage 0.0 to 255.0 200.0 V A A − 31B — E3-06 Motor 2 Base Frequency 0.0 to E3- 04 50 Hz A A − 31C — E3-07 Motor 2 Mid Output Freq.

0.0 to E3- 04 2.5 Hz A A − 31D — E3-08 Motor 2 Mid Output Freq. Voltage 0.0 to 255.0 16.0 V A A − 31E — VACrms Out (V) E3-05 E3-12 E3-13 E3-08 E3-10 E3-09 E3-07 E3-06 E3-11 E3-04 Frequency (Hz) E3-09 Motor 2 Min. Output Freq. 0.0 to E3- 04 1.3 Hz A A − 31F — E3-10 Motor 2 Min. Output Freq. Voltage 0.0 to 255.0 12.0 V A A − 320 — E3-11 Motor 2 Mid Output Frequency 2 0.0 to E3- 04 0.0 Hz A A − 345 — E3-12 Motor 2 Mid Output Frequency Voltage 2 0.0 to 255.0 0.0 Vac A A − 346 — E3-13 Motor 2 Base Voltage 0.0 to 255.0 0.0 Vac A S − 347 — E4: Motor 2 Parameters Use E4 parameters to control a second motor operating on the same drive.

E4-01 Motor 2 Rated Current Sets the motor 2 name plate full load current in amperes (A). This value is automatically set during Auto-Tuning. 10 to 200% of drive rated current A A − 321 — E4-02 Motor 2 Rated Slip Sets the motor 2 name plate full load current in amperes (A). Automatically set during Auto-Tuning. 0.00 to 20.00 A A − 322 — E4-03 Motor 2 Rated No-Load Current Sets the magnetizing current of motor 2 in Ampere. Automatically set during Rotational Auto-Tuning. 0 to less than [E4-01] A A − 323 —