B.2 Parameter Table 316 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f OL V PM E2-05 Motor Line-to-Line Resistance Sets the phase-to-phase motor resistance in ohms. Automatically set during Auto-Tuning. 0.000 to 65.000 A A − 312 — E2-06 Motor Leakage Inductance Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. Automatically set during Auto-Tuning. 0.0 to 40.0 A A − 313 — E2-07 Motor Iron-Core Saturation Coefficient 1 Sets the motor iron saturation coefficient at 75% of magnetic flux. Automatically set during Auto-Tuning.
E2-07 to 0.50 0.50 − A − 314 — E2-08 Motor Iron-Core Saturation Coefficient 2 Sets the motor iron saturation coefficient at 75% of magnetic flux. Automatically set during Auto-Tuning. [E2-07] to 0.75 0.75 − A − 315 — E2-09 Motor Mechanical Loss Sets the motor mechanical loss as a percentage of motor rated power (kW). Adjust in the following circumstances: When there is a large amount of torque loss due to motor bearing friction. When there is a large amount of torque loss. 0.0 to 10.0 0.0% − A − 316 — E2-10 Motor Iron Loss for Torque Compensation Sets the motor iron loss in watts (W). 0 to 65535 A − − 317 — E2-11 Motor Rated Output Sets the motor rated power in kilowatts (kW).
Automatically set during Auto-Tuning. (1HP = 0.746 kW). 0.00 to 650.00 0.40 kW S S − 318 380 E2-12 Motor Iron-Core Saturation Coefficient 3 Set to the motor iron saturation coefficient at 130% of magnetic flux. Automatically set during rotational Auto-Tuning. 1.30 to 5.00 1.30 − A − 328 — E3: Motor 2 V/f Characteristics Use E3 parameters to set the V/f pattern for a second motor. E3-01 Motor 2 Control Method 0: V/f Control 2: Open Loop Vector (OLV) 0 or 2 0 A A − 319 —