B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 315 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f OL V PM E1-04 Max Output Frequency These parameters are only applicable when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. Ensure that the four frequencies are set according to these rules:
E1-04 ≥ E1-06> E1-07 ≥ E1-09 40.0 to 400.0 50 Hz S S S 303 134 E1-05 Max Output Voltage 0.0 to 255.0 200 V S S S 304 134 E1-06 Base Frequency 0.0 to E1- 04 50 Hz S S S 305 134 E1-07 Mid Output Frequency 0.0 to E1- 04 2.5 Hz A A - 306 — E1-08 Mid Output Frequency Voltage 0.0 to 255.0 16.0 V A A - 307 — VACrms Out(V) E1-05 E1-12 E1-13 E1-08 E1-10 E1-09 E1-07 E1-06 E1-11 E1-04 Frequency (Hz) E1-09 Minimum Output Freq. 0.0 to E1- 04 1.3 Hz S S S 308 134 E1-10 Minimum Output Freq.
Voltage 0.0 to 255.0 12.0 V A A - 309 — E1-11 Mid Output Frequency 2 0.0 to E1- 04 0.0 Hz A A - 30A — E1-12 Mid Output Frequency Voltage 2 0.0 to 255.0 0.0 V A A - 30B — E1-13 Base Voltage 0.0 to 255.0 0.0 V A S - 30C — E2: Motor Parameters Use E2 parameters to set motor-related data. E2-01 Motor Rated Current Sets the motor nameplate full load current in amperes (A). Automatically set during Auto-Tuning. 10 to 200% of drive rated current S S − 30E 379 E2-02 Motor Rated Slip Sets the motor rated slip in Hertz (Hz). Automatically set during rotational Auto-Tuning. 0.00 to 20.00 A A − 30F — E2-03 Motor No-Load Current Sets the magnetizing current of the motor in Ampere.
Automatically set during rotational Auto-Tuning. 0 to less than E2-01 A A − 310 — E2-04 Number of Motor Poles Sets the number of motor poles. Automatically set during Auto-Tuning. 2 to 48 4 poles A A − 311 —