omron — E: Motor Parameters

B.2 Parameter Table ◆ E: Motor Parameters 314 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f OL V PM E1: V/f Pattern Characteristics Use E1 parameters to set V/f characteristics for the motor. E1-01 Input Voltage Setting This parameter must be set to the power supply voltage. It sets the maximum and base voltage used by preset V/f patterns (E1-03 = 0 to E) and adjusts levels used by certain functions. Refer to page 130 for details WARNING! Drive input voltage (not motor voltage) must be set in E1-01 for the protective features of the drive to function properly.

failure to do so may result in equipment damage and/or death or personal injury. 155 to 255 200 V S S S 300 133 E1-03 V/f Pattern Selection Selects a preset V/f pattern. 0: 50 Hz Constant torque 1 1: 60 Hz Constant torque 2 2: 60 Hz Constant torque 3 (50Hz base) 3: 72 Hz Constant torque 4 (60 Hz base) 4: 50 Hz Variable torque 1 5: 50 Hz Variable torque 2 6: 60 Hz Variable torque 3 7: 60 Hz Variable torque 4 8: 50 Hz High starting torque 1 9: 50 Hz High starting torque 2 A: 60 Hz High starting torque 3 B: 60 Hz High starting torque 4 C: 90 Hz (60 Hz base) D: 120 Hz (60 Hz base) E: 180 Hz (60 Hz base) F: Custom V/f. E1-04 through E1-13 settings define the V/f pattern. 0 to F F A A − 302 —