omron — d: References

B.2 Parameter Table Parameter List B Default setting value is dependent on parameter o1-03, Digital Operator Display Selection. Range upper limit is dependent on parameters E1-04, Maximum Output Frequency, and d2-01, Frequency Reference Upper Limit. Parameter can be changed during run. OYMC TOEP C71060622-01-OY V1000 User Manual 313 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M d4-10 Up/Down Frequency Reference Limit Selection Selects which value is used as frequency reference lower limit if the Up/Down function is used. 0: The lower limit is determined by d2-02 or analog input (H3-02/10 = 0). The higher of both values becomes the reference limit. 1:

The lower limit is determined by d2-02. 0 or 1 0 A A A 2B6 — d4-11 Bi-directional Output Selection Enables or disables conversion of frequency reference or PID output value into bi-directional internal frequency reference. 0: Disabled - 0 to 100% reference or PID output: Operation in selected direction 1: Enabled - 50% reference or PID output: Operation in selected direction 0 or 1 0 A A A 2B7 d4-12 Stop Position Gain Sets the gain used by the simple positioning stop function to fine adjust the position. 0.50 to 2.55 1.00 A A A 2B8 d7: Offset Frequency Use d7 parameters to set the offset frequency.

d7-01 Offset Frequency 1 Added to the frequency reference when the digital input “Frequency Offset 1” (H1- = 44) is switched on. -100.0 to +100.0 0.0% A A A 2B2 — d7-02 Offset Frequency 2 Added to the frequency reference when the digital input “Frequency Offset 2” (H1- = 45) is switched on. -100.0 to +100.0 0.0% A A A 2B3 — d7-03 Offset Frequency 3 Added to the frequency reference when the digital input “Frequency Offset 3” (H1- = 46) is switched on. -100.0 to +100.0 0.0% A A A 2B4 —