B.2 Parameter Table If using a Yaskawa pico motor, the default setting is 1800 r/min. Parameter ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output Frequency Voltage 2, are set to 0. Default setting depends on the control mode for motor 2 set in parameter E3-01. The given value is for V/f control. Default setting value is dependent on parameter o2-04, Drive Unit Selection and C6-01, Drive Duty Selection. ◆ F: Options F parameters are used to program the drive for PG feedback and to function with option cards. Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 321 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M F1:

Simple PG V/f Parameters Use F1 parameters to set up the drive for Simple PG V/f control. These parameters are enabled only when H6-01 = 03 F1-02 Operation Selection at PG Open Circuit (PGO) Sets stopping method when a PG open circuit fault (PGO) occurs. Refer to parameter F1-14. 0: Ramp to Stop - Decelerate to stop using the active deceleration time. 1: Coast to Stop 2: Fast-stop - Decelerate to stop using the deceleration time in C1-09. 3: Alarm only - Drive continues operation. 0 to 3 1 A − − 381 — F1-03 Operation Selection at Overspeed (OS) Sets the stopping method when an overspeed (OS) fault occurs. Refer to F1-08 and F1-09. 0:

Ramp to stop - Decelerate to stop using the active deceleration time. 1: Coast to stop 2: Fast - Stop - Decelerate to stop using the deceleration time in C1-09. 3: Alarm Only - Drive continues operation. 0 to 3 1 A − − 382 — F1-04 Operation Selection at Deviation Sets the stopping method when a speed deviation (DEV) fault occurs. Refer to F1-10 and F1-11. 0: Ramp to stop - Decelerate to stop using the active deceleration time. 1: Coast to stop 2: Fast-stop - Decelerate to stop using the deceleration time in C1-09. 3: Alarm only - Drive continues operation.

0 to 3 3 A − − 383 — F1-08 Overspeed Detection Level Sets the speed feedback level which has to be exceeded for the time set in F1-09 before an OS fault will occur. Set as a percentage of the maximum output frequency (E1-04). 0 to 120 115% A − − 387 —