omron — H Parameters: Multi-Function Terminals

B.2 Parameter Table 328 OYMC TOEP C71060622-01-OY V1000 User Manual H1 Multi-Function Digital Input Selections H1- Setting Function Description Control Mode Pg. V/f OL V PM 44 Offset Frequency 1 Addition Closed: Adds d7-01 to the frequency reference. O O O — 45 Offset Frequency 2 Addition Closed: Adds d7-02 to the frequency reference. O O O — 46 Offset Frequency 3 Addition Closed: Adds d7-03 to the frequency reference. O O O — 60 DC Injection Braking Command Closed: Triggers DC Injection Braking (b2-02) O O - — 61 External Search Command 1 Closed: Activates Current Detection Speed Search from the max. output frequency (E1-04) if b3-01=0.

Activates Speed Estimation Type Speed search if b3-01 =1. O O O — 62 External Search Command 2 Closed: Activates Current Detection Speed Search from the frequency reference b3-01=0. Activates Speed Estimation Type Speed search if b3-01 =1. O O O — 65 KEB Ride-Thru 1 (N.C.) Open: KEB Ride-Thru 1 enabled Closed: Normal operation O O O — 66 KEB Ride-Thru 1 (N.O.) Open: Normal operation Closed: KEB Ride-Thru 1 enabled O O O — 67 Communications Test Mode Tests the MEMOBUS/Modbus RS-485/422 interface. O O O — 68 High-Slip Braking Closed: High-Slip braking is executed. Drive stops. O - - — 6A Drive Enable Open: Drive disabled.

If this input is opened during run, then the drive will stop as specified by parameter b1-03. Closed: Ready for operation. O O O — 75 Up 2 Command Open: Maintains the current frequency reference Closed: Increases or decreases the frequency reference.UP 2 and Down 2 commands must be set in combination with each other. The frequency reference source must be assigned to the operator (b1-01 = “0”). O O O — 76 Down 2 Command O O O — 7A KEB Ride-Thru 2 (N.C.) Open: KEB Ride-Thru 2 enabled Closed: Normal operation O O O — 7B KEB Ride-Thru 2 (N.O.) Open: Normal operation Closed: KEB Ride-Thru 2 enabled O O O — 7C Short-Circuit Braking (N.O.) Open: Normal operation Closed:

Short-Circuit Braking - - O — 7D Short-Circuit Braking (N.C.) - - O — 7E Forward/Reverse Detection Direction of rotation detection (for Simple V/f w/PG) O - - — 7F Bi-directional PID output selection Enables or disables conversion of PID output to bi- directional reference if parameter d4-11 = 1. Open: Bi-directional output disabled Closed: Bi-directional output enabled O O O — 9F FBD’s enable Open: FBD’s enabled Closed: FBD’s disabled O O O —