omron — H Parameters: Multi-Function Terminals

B.2 Parameter Table The availability of certain functions depends on the control method used. Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 329 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M H2: Multi-Function Digital Outputs Use H2 parameters to assign functions to the multi-function digital outputs. H2-01 Terminal MA, MB and MC Function Selection (relay) Refer to “Multi-Function Digital Output Selection Table” for a description of setting values.

0 to 192 E A A A 40B — H2-02 Terminal P1 Function Selection (open-collector) 0 A A A 40C — H2-03 Terminal P2 Function Selection (open-collector) 2 A A A 40D — H2-06 Watt Hour Output Unit Selection Sets the display units for one of the multi-function output terminals that is assigned to output the watt hours (H2- = 39) is the value every 200 ms. An output pulse of 200 ms is provided for every kWh that occurs. Intended to drive a counter, meter or PLC for logging kWh. 0: 0.1 kWh units 1: 1 kWh units 2: 10 kWh units 3: 100 kWh units 4: 1000 kWh units 0 to 4 0 A A A 437 — H2 Multi-Function Digital Output Settings H2- Setting Function Description Control Mode Pg. V/f O LV P M 0 During Run Closed:

A Run command is active or voltage is output. O O O — 1 Zero Speed Closed: Output frequency is 0. O O O — 2 Fref/Fout Agree 1 Closed: Output frequency equals the speed reference (plus or minus the hysteresis set to L4-02). O O O — 3 Fref/Fset Agree 1 Closed: Output frequency and speed reference equal the value in L4-01 (plus or minus the hysteresis of L4-02). O O O — 4 Frequency (FOUT) Detection 1 Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis determined by L4-02. O O O — 5 Frequency (FOUT) Detection 2 Closed: Output frequency is greater than or equal to the value in L4-01, with hysteresis determined by L4-02. O O O —