omron — H Parameters: Multi-Function Terminals

B.2 Parameter Table 330 OYMC TOEP C71060622-01-OY V1000 User Manual H2 Multi-Function Digital Output Settings H2- Setting Function Description Control Mode Pg. V/f O LV P M 6 Drive Ready Closed: Drive Ready. The drive is powered up, not in a fault state, and in the Drive mode. O O O — 7 DC Bus Undervoltage Closed: DC bus voltage is below the UV trip level set in L2-05. O O O — 8 During Baseblock Closed: There is no output voltage O O O — 9 Frequency reference selection Open: External Reference 1 or 2 supplies the frequency reference Closed: Digital operator supplies the frequency reference. O O O — A Run command selection Open: External Reference 1 or 2 supplies the Run command Closed:

Digital operator supplies the Run command. O O O — B Torque Detection 1 (N.O.) Closed: Output current/torque exceeds the torque value set in parameter L6-02 for longer than the time set in parameter L6-03. O O O — C Loss of Reference Closed: Loss of the analog frequency reference detected. Enabled when L4-05 = 1. O O O — D Braking Resistor Fault Closed: Braking resistor or transistor is overheated or faulted out. This selection requires that braking resistor protection parameter be set for ERF (L8-01 = “1”). O O O — E Fault Closed: Fault occurred (other than CPF00 and CPF01). O O O — F Not used Set this value when the terminal is not used, or when using the terminal in the pass-through mode.

O O O — 10 Alarm Closed: An alarm is triggered. O O O — 11 Reset Command Active Closed: Reset command to the drive is active. O O O — 12 Timer Output Timer output, controlled by b4-01 and b4-02. Used in conjunction with the digital input (H1-†† = 18 “timer function”). O O O — 13 Fref/Fout Agree 2 Closed: When drive output frequency equals the frequency reference +/- L4-04. O O O — 14 Fref/Fset Agree 2 Closed: When the drive output frequency is equal to the value in L4-03 (plus or minus L4-04). O O O — 15 Frequency Detection 3 Closed: When the drive output frequency is less than or equal to the value in L4-03 with the hysteresis determined by L4-04. O O O — 16 Frequency Detection 4 Closed:

When the output frequency is greater than or equal to the value in L4-03 with the hysteresis determined by L4-04. O O O — 17 Torque Detection 1 (N.C.) Open: When the output current/torque exceeds the value set in parameter L6-02 for more time than is set in parameter L6-03. O O O — 18 Torque Detection 2 (N.O.) Closed: When the output current/torque exceeds the value set in parameter L6-05 for more time than is set in parameter L6-06. O O O — 19 Torque Detection 2 (N.C.) Open: Output current/torque exceeds the value set in parameter L6- 05 for more time than is set in parameter L6-06. O O O — 1A Reverse Direction Closed: Drive is running in the reverse direction. O O O —